Skip to content

Free shipping on orders over $99.

8:30 to 5 ET(704) 555-0142
Not sure what you have? Send the part number(704) 555-0142
Det-Tronics Det-Tronics DE5434-004 (005434-004) H2S EC Cell 0-50PPM view 1

Det-Tronics DE5434-004 (005434-004) H2S EC Cell 0-50PPM

Det-Tronics
$222.28
In stock — 32 available
In stock · ready to ship
Ships today — order before 3:00 PM ET
Delivery in 3–5 business days
Ships from the USA — free shipping over $99
BrandDet-Tronics
SKU005434-004
TypeSensors
Variants1

Det-Tronics 005434-004 (DE5434-004) is the replacement electrochemical sensor cell for hydrogen sulfide (H2S), 0 to 50 ppm range, used in the C7064E detector. The cell uses capillary diffusion barrier technology and is highly specific to H2S, with little cross-sensitivity to common gases.

Specifications

Part number 005434-004 (DE5434-004)
Gas Hydrogen sulfide (H2S)
Range 0 to 50 ppm
Fits C7064E detector housing
Detector accuracy ±10% of applied gas or ±3 ppm, whichever is greater
Detector response time T20 ≤ 12 s, T50 ≤ 30 s
Detector stability Zero < 1 ppm/month; span < 1% FS/month
Weight 2 oz (0.09 kg)

Installation notes

  • The cell is not field repairable; replace it when calibration can no longer be performed
  • De-classify the area or remove power before replacing the sensor in a hazardous area
  • Keep the cell in its sealed bag in a cool place until commissioning
  • Check the hydrophobic filter (004532-002) before replacing the cell
  • Calibrate 24 hours after power-up, one week later, then about every 30 days

The other C7064E ranges use 005434-003 (0 to 20 ppm) and 005434-002 (0 to 100 ppm). Scale the 4-20 mA input to match the cell range.

Questions about this product

Is Det-Tronics DE5434-004 (005434-004) H2S EC Cell 0-50PPM in stock?

Yes — 32 units are available and ready to ship from our US warehouse.

How fast will Det-Tronics DE5434-004 (005434-004) H2S EC Cell 0-50PPM ship?

Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.

Where does Det-Tronics DE5434-004 (005434-004) H2S EC Cell 0-50PPM ship from?

It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.