Det-Tronics DE5434-004 (005434-004) H2S EC Cell 0-50PPM
| Brand | Det-Tronics |
|---|---|
| SKU | 005434-004 |
| Type | Sensors |
| Variants | 1 |
Det-Tronics 005434-004 (DE5434-004) is the replacement electrochemical sensor cell for hydrogen sulfide (H2S), 0 to 50 ppm range, used in the C7064E detector. The cell uses capillary diffusion barrier technology and is highly specific to H2S, with little cross-sensitivity to common gases.
Specifications
| Part number | 005434-004 (DE5434-004) |
| Gas | Hydrogen sulfide (H2S) |
| Range | 0 to 50 ppm |
| Fits | C7064E detector housing |
| Detector accuracy | ±10% of applied gas or ±3 ppm, whichever is greater |
| Detector response time | T20 ≤ 12 s, T50 ≤ 30 s |
| Detector stability | Zero < 1 ppm/month; span < 1% FS/month |
| Weight | 2 oz (0.09 kg) |
Installation notes
- The cell is not field repairable; replace it when calibration can no longer be performed
- De-classify the area or remove power before replacing the sensor in a hazardous area
- Keep the cell in its sealed bag in a cool place until commissioning
- Check the hydrophobic filter (004532-002) before replacing the cell
- Calibrate 24 hours after power-up, one week later, then about every 30 days
The other C7064E ranges use 005434-003 (0 to 20 ppm) and 005434-002 (0 to 100 ppm). Scale the 4-20 mA input to match the cell range.
Questions about this product
Is Det-Tronics DE5434-004 (005434-004) H2S EC Cell 0-50PPM in stock?
Yes — 32 units are available and ready to ship from our US warehouse.
How fast will Det-Tronics DE5434-004 (005434-004) H2S EC Cell 0-50PPM ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Det-Tronics DE5434-004 (005434-004) H2S EC Cell 0-50PPM ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.