Det-Tronics 007168-005 (model PIRECLA1B1W2) is a PointWatch Eclipse PIRECL diffusion-based infrared combustible gas detector for continuous monitoring of flammable hydrocarbon gases from 0 to 100% LFL. It is built for onshore and offshore oil and gas facilities and other hydrocarbon applications, with an explosion-proof 316 stainless steel housing, heated sapphire optics and a tethered weather baffle. Integral wiring compartment and tri-color LED remove the need for external junction boxes and display modules.
Specifications
| Detection range | 0 to 100% LFL standard |
| Calibrated gases | Methane, propane, ethylene or butane (factory set) |
| Outputs | Isolated 4-20 mA with HART; RS-485 MODBUS/ASCII |
| Input voltage | 18 to 32 VDC (24 VDC nominal) |
| Power | 4.0 W nominal, 7.5 W max @ 24 VDC |
| Alarm setpoints | 5 to 60% LFL |
| Accuracy | ±3% (0-50% LFL), ±5% (51-100% LFL) |
| Operating temperature | -67°F to +167°F (-55°C to +75°C) |
| Housing | 316 stainless steel; IP66/IP67 |
| Conduit entries | Two, 3/4 in. NPT or 25 mm |
| Dimensions | 9.3 x 5.2 x 4.6 in. |
| Shipping weight | 10.5 lb (4.8 kg) |
| Certifications | FM, CSA, ATEX, IECEx, DNV, INMETRO; Class I Div. 1 Groups B, C, D |
Features
- Routine calibration not required; immune to damage from high gas concentrations
- Self-diagnostic tests performed once per second
- Optional relay board with two alarm relays and one fault relay
- SIL 2 certified models per IEC 61508
- Remote calibration with optional FlexVu UD10, UD20 or UD30 display
Related models
- Other PointWatch Eclipse PIRECL configurations under the 007168 part number family.
Documents
FAQ
Which gases does it detect?
Most flammable hydrocarbon gases and vapors from 0 to 100% LFL. It is performance certified to methane, propane, ethylene and butane and ships factory set and calibrated to one of these.
Does it need routine calibration?
Det-Tronics states routine calibration is not required.
What outputs does it provide?
An isolated 4-20 mA signal with HART, plus RS-485 serial (MODBUS and ASCII). An optional relay board adds two alarm relays and one fault relay.
Where can it be installed?
It is certified for Class I, Divisions 1 and 2, and Zones 1 and 2 hazardous areas, with operating temperature from -67°F to +167°F.
Questions about this product
Is Det-Tronics PIRECLA1B1W2 (007168-005) PointWatch Eclipse Infrared Gas Detector in stock?
Yes — 10 units are available and ready to ship from our US warehouse.
How fast will Det-Tronics PIRECLA1B1W2 (007168-005) PointWatch Eclipse Infrared Gas Detector ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Det-Tronics PIRECLA1B1W2 (007168-005) PointWatch Eclipse Infrared Gas Detector ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.