Det-Tronics X3301S4N15W1 (028114-001) Multispectrum Infrared Flame Detector
| Brand | Det-Tronics |
|---|---|
| SKU | 028114-001 |
| Type | Flame Detectors |
| Variants | 1 |
Det-Tronics X3301S4N15W1 (028114-001) is an X3301 multispectrum infrared (MSIR) flame detector in a 316 stainless steel housing. It is designed for fast detection of hydrocarbon and other fuel fires with strong rejection of false alarm sources, for offshore platforms, gas turbine enclosures, aircraft hangars and other high hazard areas.
The pulse/relay output version can serve as a direct field replacement for Det-Tronics controller based flame detectors that use a pulse output (not compatible with R7484 and R7409B/C). Microprocessor-controlled heated optics keep the window clear in wet and cold conditions.
Specifications
| Detection | Multispectrum infrared |
| Range | Methane 32 in. plume: 125 ft (38.1 m); n-heptane 1 x 1 ft: up to 250 ft (76.2 m), very high sensitivity |
| Field of view | 90° horizontal x 75° vertical |
| Operating voltage | 24 Vdc nominal, 18 to 30 Vdc |
| Power | 4 W minimum without heater; 17 W at 30 Vdc with heater on maximum |
| Relays | Fire alarm Form C and fault Form A, 5 A at 30 Vdc |
| Operating temperature | -40 °F to +167 °F (-40 °C to +75 °C) |
| Humidity | 0 to 95% RH |
| Enclosure | 316 stainless steel, NEMA/Type 4X, IP66/IP67 |
| Conduit entries | 3/4 in. NPT |
| Wiring | 16 AWG (2.5 mm²) shielded cable recommended |
| Hazardous locations | Class I, Div. 1, Groups B, C, D; Ex d e IIC (increased safety) or Ex d IIC |
| Shipping weight | 13.8 lb (6.3 kg) stainless steel |
| Warranty | 5 years |
Features
- Multispectrum IR detection with maximum false alarm rejection
- Reliable detection with a modulated IR background
- Pulse output for controller based systems
- Microprocessor-controlled heated optics
- Easily retrofitted in place of R7404 and R7494 based detectors
Related models
- 028262-001: another X3301 multispectrum IR flame detector configuration
Documents
FAQ
What fires does the X3301 detect, and how far?
It detects hydrocarbon fuel fires and other fuels such as methanol and ethanol. At very high sensitivity Det-Tronics rates a 1 x 1 ft n-heptane fire at up to 250 ft (76.2 m) and a 32 in. methane plume at 125 ft (38.1 m).
What outputs does the pulse version have?
A Form C fire alarm relay and a Form A fault relay, both rated 5 A at 30 Vdc, plus a pulse output for controller based systems.
What power does it need?
24 Vdc nominal (18 to 30 Vdc), 4 watts minimum without heater and up to 17 watts at 30 Vdc with the heater on maximum.
What is the field of view?
90° horizontal by 75° vertical, at a minimum of 70% of the on-axis detection distance.
Questions about this product
Is Det-Tronics X3301S4N15W1 (028114-001) Multispectrum Infrared Flame Detector in stock?
Yes — 13 units are available and ready to ship from our US warehouse.
How fast will Det-Tronics X3301S4N15W1 (028114-001) Multispectrum Infrared Flame Detector ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Det-Tronics X3301S4N15W1 (028114-001) Multispectrum Infrared Flame Detector ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.