DITEK DTK-KG2 Kool Guard 2 Intelligent Voltage Monitor, 120/240 VAC split phase, 40 A MCA, NEMA 4X
| Brand | DITEK |
|---|---|
| SKU | DTK-KG2 |
| Type | Surge Protection Devices |
| Variants | 1 |
DITEK DTK-KG2 — Kool Guard intelligent voltage monitor for HVAC equipment, with board-level surge protection in a UL Type 4X enclosure.
It is not only a surge protector. Wired in series between the load side of the disconnect and the equipment, it watches each phase to ground independently and cuts power when the supply leaves the normal band. Two pairs of red and green LEDs report the condition without opening the lid, and a Service Required pattern means the surge components have expired.
- 120/240 VAC or 120/208 VAC split phase, equipment up to 40 A MCA
- Undervoltage below 104 V line to ground, overvoltage above 130 V
- Detection in 1/60th second; phase imbalance detection
- Short cycle delay 3 minutes default, 30 seconds by jumper P7
- 50,000 A surge current rating
- Lugs 14 to 6 AWG, 1/2" or 3/4" NPT conduit, 6.25" × 6.25" × 2.62"
- UL and CSA to 60947-1 and 60947-5-1, RoHS
DITEK lists no DTK-KG1; the 2 belongs to the name Kool Guard 2. DITEK compares it against the Rectorseal RSH-50 VRM Kit and ICM Controls ICM 493, both NEMA 3R and line-to-line only.
Documents
FAQ
What equipment is the DTK-KG2 designed for?
HVAC equipment such as inverter-driven systems, condensing units and ductless systems, with a minimum circuit ampacity (MCA) rating up to 40 A.
At what voltages does it disconnect power?
It monitors each phase line-to-ground and disconnects below 104 V or above 130 V. Power is restored once the input returns to the normal range.
Is there a restart delay?
Yes. A short cycle delay timer defaults to 3 minutes and can be set to 30 seconds.
Can it be installed outdoors?
Yes. It comes in a UL Type 4X polycarbonate enclosure for harsh outdoor environments.
Questions about this product
Is DITEK DTK-KG2 Kool Guard 2 Intelligent Voltage Monitor, 120/240 VAC split phase, 40 A MCA, NEMA 4X in stock?
Yes — 20 units are available and ready to ship from our US warehouse.
How fast will DITEK DTK-KG2 Kool Guard 2 Intelligent Voltage Monitor, 120/240 VAC split phase, 40 A MCA, NEMA 4X ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does DITEK DTK-KG2 Kool Guard 2 Intelligent Voltage Monitor, 120/240 VAC split phase, 40 A MCA, NEMA 4X ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.