Fire-Lite MMF-302-6 6INPUT Class B or 3INPUT Class a 2WIRE DET Zone Module
| Brand | Fire-Lite |
|---|---|
| SKU | MMF-302-6 |
| Type | Modules |
| Variants | 1 |
Fire-Lite MMF-302-6 is a six-zone addressable interface module that connects conventional two-wire detection zones to an intelligent alarm system. It supports six Class B or three Class A initiating device circuits.
It reports each zone's status to the fire alarm control panel as normal, open or alarm. All six zones share one SLC input and a common external supervisory supply and ground, and otherwise each works independently. Two-wire detectors on the zones must be listed as compatible with the module.
Features
- Six Class B or three Class A initiating device circuits
- Reports normal, open or alarm status for each zone
- Supervises the detector zone and the external power supply connection
- Removable plug-in terminal blocks
- Panel-controlled bicolor LED indicators for each point
- Rotary address switches; first module set from 01 to 154, the next five addressed automatically
- Up to two unused modules can be disabled
Specifications
| Product type | Addressable monitor module |
| Zones | 6 Class B or 3 Class A |
| Height | 6.8" |
| Width | 5.8" |
| Depth | 1.3" |
Documents
- MMF-302-6(A) Six-Zone Interface Module — Data Sheet (PDF)
- MMF-302-6 Six Zone Interface Module Installation Instructions (PDF)
FAQ
How is the MMF-302-6 mounted?
One or two modules mount in a BB-2F cabinet, or up to six modules on a CH-6 chassis in a BB-6F cabinet; mounting hardware is included.
How are the addresses set?
The first module is addressed from 01 to 154 with rotary switches; the remaining five are assigned automatically to the next five higher addresses.
Is it shipped for Class A or Class B?
It ships in the Class B position; remove the shunt for Class A operation.
How much SLC current does it draw?
2.0 mA standby with all addresses used, and 40 mA in alarm with all six LEDs on.
Questions about this product
Is Fire-Lite MMF-302-6 6INPUT Class B or 3INPUT Class a 2WIRE DET Zone Module in stock?
Yes — 17 units are available and ready to ship from our US warehouse.
How fast will Fire-Lite MMF-302-6 6INPUT Class B or 3INPUT Class a 2WIRE DET Zone Module ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Fire-Lite MMF-302-6 6INPUT Class B or 3INPUT Class a 2WIRE DET Zone Module ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.