Li-ion Tamer LT-SEN-IM-UL — Interface Module UL for the Xtralis Li-ion Tamer Sensor Multi Output Solution (MOS) off-gas detection system.
The Gen 2+ off-gas sensor head is a small RJ45 device with no outputs of its own. This module converts its detection of hydrogen, carbon monoxide and battery electrolyte solvent vapor into contacts and serial data a fire panel or battery management system can act on — to isolate the string and start ventilation before thermal runaway.
- Three relays (alarm 1, alarm 2, fault), Modbus RTU and CANbus
- Relay load max. 30 VDC 2 A, or 125 VAC 0.5 A
- 15–32 VDC (24 VDC typical); 65 mA, 1.56 W max. with sensor
- One sensor per module; up to 12 modules daisy-chained, EOL resistor on the last
- 140 × 85 × 34 mm; UL 864 10th ed., ULC S527, FM 6540
Spare-part module only — a complete system is ordered as LT-SEN-MOS or LT-SEN-MOS-C49, which pairs it with a sensor. It needs an installer-supplied junction box, and for UL 864 compliance the alarm relay must stay normally open.