Mircom FX-4003-12N — FleX-Net FX-4000N Series compact main network fire alarm control unit, 12 A. The display, backbox and door are sold separately.

The FX-4003-12N is the main processor chassis of a modular, multi-protocol FleX-Net system. It handles fire detection and alarm, audio/voice evacuation, BACnet, Boolean logic, networking and graphical workstation support, from simple systems up to complex networked projects.

Specifications

Protocols MIX-4000 devices, Advanced Protocol (AP), CLIP
SLCs Expandable up to 8; 200 mA standby and 400 mA alarm per SLC
SLC capacity Up to 240 MIX-4000 devices, or 318 AP devices (159 sensors and 159 modules) per SLC
NACs Four Class A/B, 1.7 A each, built-in sync
Primary power 120 VAC 60 Hz, 4 A / 240 VAC 50 Hz, 2 A
Batteries 24 VDC gel cell or sealed lead acid
Event history 5,000 alarm events and 5,000 total events
Displays 80-character LCD (DSPL-420DS) or 640-character color display, sold separately

Features

  • Main board with built-in network interface, voice evacuation interface and IP port for OpenGN or BMS integration
  • Built-in BACnet and web server for remote event notification and diagnostics
  • Up to 7 remote annunciators per node; RS-232 printer port and RS-485 expansion port
  • Configuration changes without taking the panel off-line, with current, previous and next configuration files
  • Conventional detectors supported through the DM-1008A or MIX-4042 modules

Installation notes

  • Order the main display, backbox and door separately.
  • SLC maximum line resistance is 40 ohms and maximum capacitance 0.47 µF.

Documents

FAQ

Is the display included?
No. The display, backbox and door are sold separately. The DSPL-420DS is the 4 x 20 main LCD display for the FX-4003-12N.

How many SLCs can it have?
It is expandable up to 8 SLCs, each rated 200 mA standby and 400 mA alarm.

Which device protocols does it support?
Mircom MIX-4000 devices, Advanced Protocol (AP) and CLIP.

How many NACs are on board?
Four Class A/B notification appliance circuits rated 1.7 A each, with built-in sync protocol.

Questions about this product

Is Mircom FX-4003-12N FleX-Net Compact Main Network Fire Alarm Control Unit, 12 Amp, Display, Backbox and Door Sold Separately in stock?

Yes — 35 units are available and ready to ship from our US warehouse.

How fast will Mircom FX-4003-12N FleX-Net Compact Main Network Fire Alarm Control Unit, 12 Amp, Display, Backbox and Door Sold Separately ship?

Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.

Where does Mircom FX-4003-12N FleX-Net Compact Main Network Fire Alarm Control Unit, 12 Amp, Display, Backbox and Door Sold Separately ship from?

It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.

Cart0
Your cart is empty

Have an account? Log in to check out faster.

Continue shopping