Notifier NZM-100-6 Six Zone Interface Module

Notifier
$116.11
In stock — 10 available
In stock · ready to ship
Ships today — order before 3:00 PM ET
Delivery in 3–5 business days
Ships from the USA — free shipping over $99
BrandNotifier
SKUNZM-100-6
TypeModules
Variants1

Notifier NZM-100-6 is a six-zone interface module for FireWarden series addressable panels. It connects the intelligent system to two-wire conventional detection zones.

A common SLC input serves all six modules, and the initiating device circuits share a common external supervisory supply and ground; otherwise each module operates independently. The first module is addressed from 01 to 94 and the others take the next five higher addresses. Each reports its zone as normal, open or alarm and supervises the zone and the external supply.

Specifications

Circuits 6 Class B or 3 Class A IDCs
Addressing Rotary switches, first module 01–94
Standby current 2.0 mA
Alarm current 40 mA, all six LEDs on
External supply 18–28 VDC power limited, 90 mA per address in alarm
Max IDC resistance 25 ohms
Wire gauge 12–18 AWG
Dimensions 6.8 x 5.8 x 1.25 in.
Temperature 32 to 120 °F

Installation notes

  • Shipped in the Class B position; remove the shunt for Class A operation
  • Mount one or two modules in a BB-XP cabinet
  • Mount up to six modules on a CHS-6 chassis in a CAB-3, CAB-4 or BB-25 cabinet
  • Up to two unused addresses can be disabled
  • Two-wire detectors must be compatible per the Notifier Device Compatibility Document

Related models

  • NZM-100-6A: same module, ULC version
  • XP6-MA: six-zone interface module for ONYX FlashScan and CLIP panels
  • NFW-100X: FireWarden addressable panel

Documents

FAQ

Which panels use the NZM-100-6?
NOTIFIER FireWarden series addressable panels. For ONYX panels the comparable module is the XP6-MA.

Does it need external power?
Yes. The zones share an external 18 to 28 VDC power-limited supply, up to 540 mA for all six addresses in alarm in Class B.

Can it run Class A?
Yes. It ships in the Class B position; remove the shunt to run three Class A circuits.

What enclosure do I need?
One or two modules fit a BB-XP cabinet, or up to six on a CHS-6 chassis in a CAB-3, CAB-4 or BB-25 cabinet.

Questions about this product

Is Notifier NZM-100-6 Six Zone Interface Module in stock?

Yes — 10 units are available and ready to ship from our US warehouse.

How fast will Notifier NZM-100-6 Six Zone Interface Module ship?

Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.

Where does Notifier NZM-100-6 Six Zone Interface Module ship from?

It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.

Cart0
Your cart is empty

Have an account? Log in to check out faster.

Continue shopping