Potter EVAX-25 25 Watt Voice Panel, Charcoal Cabinet
| Brand | Potter |
|---|---|
| SKU | EVAX-25 |
| Type | Control Panels |
| Variants | 1 |
Potter EVAX-25 is a 25 W voice evacuation panel in a charcoal grey cabinet. It operates with any fire alarm control panel (FACP) and has its own 120 VAC power supply and battery charger, a built-in digital message repeater (DMR), and an integral paging microphone. The panel must be wired to 120 VAC with standby batteries connected, and it mounts in a surface or semi-flush backbox with a hinged, key-locked door.
The alarm tone, automatic message repeats and the 6-hour delay of AC power failure reporting are field configurable. Removing the microphone causes a trouble condition that is reported locally and through the FACP. A live microphone page overrides the message and tone.
Specifications
| Output | 25 W at 25 or 70 Vrms (field selectable) |
| Speaker circuit | Class A or Class B |
| Primary power | 0.8 A at 120 VAC |
| Battery current (24 VDC) | 0.18 A standby, 1.1 A alarm |
| Battery back-up | 24 hours with two 12 V 7 Ah batteries |
| Message storage | 8 MB MP3 driver |
| Backbox (W x H x D) | 14.5 x 18 x 4 in. |
| Color | Charcoal grey |
| Weight | 29 lb (13.2 kg) |
Features
- Works with 12 or 24 VDC fire alarm panels, including microprocessor-based and networked systems.
- Dead-front construction; fully supervised.
- Built-in alarm and alert signals with studio-quality voice recordings.
- 3-minute message restart on microphone key.
- A secondary message can be triggered by a contact closure from the FACP or any normally open contact device.
- Remote paging microphones can be mounted up to 5,000 ft from the panel on a supervised circuit.
- Expandable with zone splitters, selection switches, remote microphone panels and expander modules.
Related models
- EVAX-25/4Z and EVAX-25/8Z — the 25 W panel with 4 or 8 speaker zones.
- EVAX-50 — 50 W version.
- EVAX-100 — 100 W version.
Documents
FAQ
Does the EVAX-25 work with any fire alarm panel?
Yes. It operates with any fire alarm control panel and works with 12 or 24 VDC panels, including microprocessor-based and networked systems.
What batteries does it need?
It provides 24-hour back-up with two 12 V 7 Ah batteries. Battery current is 0.18 A in standby and 1.1 A in alarm.
Is a microphone included?
Yes. The paging microphone is an integral component, and removing it causes a trouble condition reported locally and through the FACP.
Can it drive more than one speaker zone?
The EVAX-25/4Z and EVAX-25/8Z versions provide 4 or 8 speaker zones. The speaker circuit is field selectable for 25 or 70 Vrms.
Questions about this product
Is Potter EVAX-25 25 Watt Voice Panel, Charcoal Cabinet in stock?
Yes — 38 units are available and ready to ship from our US warehouse.
How fast will Potter EVAX-25 25 Watt Voice Panel, Charcoal Cabinet ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does Potter EVAX-25 25 Watt Voice Panel, Charcoal Cabinet ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.