System Sensor 7351 Smoke Sensor
| Brand | System Sensor |
|---|---|
| SKU | 7351 |
| Type | Smoke Detectors |
| Variants | 1 |
System Sensor 7351 — Pinnacle Select Series high sensitivity photoelectric spot detector, white, for very early warning fire detection.
The 7351 pairs a smoke-sensing chamber and patented optic block with LED technology to reach sensitivity from 0.02 to 2.0 %/ft obscuration, up to 25 times greater than a standard photoelectric detector. Multi-alert drift compensation, self-diagnostics and transient rejection keep it stable at those levels, and analog addressable communication gives point identification of the fire location. System Sensor catalogs it as the laser detector replacement, for telecom switching sites, data centers, clean rooms, computer rooms and traffic control centers.
Specifications
| Model | 7351, white |
| Sensing | High sensitivity photoelectric |
| Sensitivity | 9 levels, 0.02 to 2.00 %/ft obscuration |
| Operating voltage | 15 to 32 VDC |
| Standby current | 300 µA at 24 VDC |
| Alarm current | 2 mA at 24 VDC |
| Operating temperature | 14 °F to 140 °F (-10 °C to 60 °C) |
| Humidity | 10% to 93% RH, non-condensing |
| Air velocity | 0 to 4,000 fpm |
| Addressing | Rotary address switches |
| Certifications | UL 268 open area and special applications; UL 268A duct |
Installation notes
- Mounts on a separately ordered base: B501-WHITE 4 in. base or B300-6 6 in. flanged base.
- Relay (B224RB-WH), isolator (B224BI-WH) and sounder (B200S-WH) bases are available for the Select Series.
- UL 268A duct use covers installation in duct and within DNR and DNRW duct smoke detector housings.
- RA100Z remote LED annunciator and M02-04-01 test magnet are available accessories.
Related models
- 5351B, 5351H and 5351RB are Select Series heat detectors.
- Bases are B501-WHITE, B300-6, B224RB-WH, B224BI-WH and B200S-WH.
Documents
- 7351 Pinnacle Select Series High Sensitivity Detector — Data Sheet (PDF)
- 7351 Installation Manual (PDF)
FAQ
Is a base included?
No. The 7351 mounts on a separately ordered base such as the B501-WHITE 4 in. base or the B300-6 6 in. flanged base.
What sensitivity range does it cover?
Nine levels from 0.02 to 2.00 %/ft obscuration. It is UL certified for open-area protection at 0.5 to 2.0 %/ft and for special applications at 0.02 to 0.5 %/ft.
Can it be used in a duct?
Yes. It is certified to UL 268A for duct applications, both in duct and within System Sensor DNR and DNRW duct housings.
What are the operating limits?
15 to 32 VDC, 14 °F to 140 °F, 10% to 93% RH non-condensing and air velocity up to 4,000 fpm.
Questions about this product
Is System Sensor 7351 Smoke Sensor in stock?
Yes — 12 units are available and ready to ship from our US warehouse.
How fast will System Sensor 7351 Smoke Sensor ship?
Orders placed before 3:00 PM ET ship the same business day. Delivery takes 3–5 business days inside the USA.
Where does System Sensor 7351 Smoke Sensor ship from?
It ships from the United States. Standard delivery is 3–5 business days, and orders placed before 3:00 PM ET go out the same day.